Proper roof drain design ensures safe drainage during heavy rainfall and prevents structural damage. This article explains the roof drain calculation formula, key variables, code references, examples, and practical tips for sizing drains, leaders, and overflow systems for U.S. buildings.
| Symbol | Meaning | Units |
|---|---|---|
| A | Drain Area | Square Feet (ft2) |
| I | Rainfall Intensity | Inches Per Hour (in/hr) |
| Q | Drain Flow Rate | Gallons Per Minute (gpm) |
| C | Runoff Coefficient | Dimensionless |
| k | Conversion Constant | 0.623 gal/(ft2·in) |
Overview Of The Roof Drain Calculation Formula
The fundamental roof drain calculation converts rainfall intensity and contributing roof area into a required discharge rate. A common and code-accepted equation is Q (gpm) = A (ft2) × I (in/hr) × 0.010383, where 0.010383 = 0.623 ÷ 60. This factor converts inches of rain over square feet into gallons per minute.
Key Variables And How To Determine Them
A (Roof Area) is the tributary area that drains to a single roof drain, measured in square feet. For sloped roofs, calculate horizontal projected area unless code requires slope correction. For multiple drains, divide the roof into tributary areas using hydraulic boundaries.
I (Rainfall Intensity) is the design rainfall rate in inches per hour for the building location and duration used by local plumbing or mechanical codes. Use the value specified by the applicable code (often from NOAA or local amendments).
C (Runoff Coefficient) is typically 1.0 for impervious roofs (metal, membrane, built-up). Green roofs, vegetated systems, or porous assemblies may have reduced effective runoff; consult manufacturer data or local code for adjustments.
Derivation And Conversion Constants
One inch of rain falling on one square foot produces 0.623 gallons. To convert a rate in inches per hour over an area to gallons per minute: Q (gpm) = A × I × 0.623 ÷ 60 = A × I × 0.010383. This conversion is accepted in plumbing and roofing practice for sizing drains and conductors.
Don’t Overpay for Roofing Services – Call 877-801-4315 Now to Compare Local Quotes!
Code References And Rainfall Intensity Sources
Plumbing and building codes referenced in the U.S. include the International Plumbing Code (IPC) and International Building Code (IBC). These specify using local rainfall intensities—commonly the 100-year short-duration intensity or the value in the authority having jurisdiction. NOAA Atlas or local design storms provide official intensity values.
Step-By-Step Roof Drain Sizing Procedure
- Determine Tributary Area (A): Map roof planes and hydraulic boundaries to assign square feet to each drain.
- Select Rainfall Intensity (I): Use the code-required in/hr for the design location and storm duration.
- Apply Formula: Q = A × I × 0.010383 to get gpm per drain.
- Check Drain/Inlet Capacity: Compare calculated Q to manufacturer’s rated capacity for the chosen roof drain size and type.
- Size Leaders/Conductors: Combine flows for all drains entering a leader; use tables or Manning calculations to size diameter.
- Provide Overflows/Scuppers: Ensure secondary overflows or scuppers can pass required emergency flow if primary drains are blocked.
Example Calculation
For a 2,400 ft2 flat membrane roof with one primary drain and a design rainfall of 3 in/hr, the required flow is Q = 2,400 × 3 × 0.010383 = 74.84 gpm. Select a roof drain and leader that can carry at least this flow, and include an overflow sized equal to or greater than this rate per code.
Sizing Multiple Drains And Tributary Areas
When more than one drain serves a roof area, assign tributary areas using hydraulic boundaries such as ridgelines, roof valleys, and slope breaks. Each drain’s tributary area is the surface that would naturally flow to that drain. Calculate Q for each drain separately and size inlets accordingly.
Leaders, Horizontal Conductors, And Storm Sewers
Flows collected by roof drains often travel through vertical leaders and horizontal storm piping. For vertical conductors, sum flows of all contributing drains and check manufacturer tables for maximum capacity given the vertical drop and inlet conditions.
For horizontal pipes, use the Darcy-Weisbach or Manning equation, or code sizing tables. Common practice uses tabulated capacities in plumbing codes that relate pipe diameter to gpm for specific slopes and materials.
Effect Of Roof Slope And Projections
Most drainage calculations use horizontal projected area. For steep-sloped roofs, project onto horizontal plane. If local code requires slope correction, multiply area by cos(theta) or use the roof area measured horizontally. Parapets and overflows must be sized for freeboard and potential ponding.
Safety Factors And Blockage Considerations
Codes often require secondary overflow devices sized to handle inadequate primary drainage due to blockage. Designers commonly apply a safety factor of 10–25% to account for debris, partial blockage, and inlet losses. Always confirm local code requirements for overflow sizing.
Don’t Overpay for Roofing Services – Call 877-801-4315 Now to Compare Local Quotes!
Special Cases: Green Roofs, Loaded Roofs, And Roof Drains With Filters
Green roofs and roofs with filters or drains fitted with strainers may reduce flow. Use manufacturer test data or adjust the runoff coefficient. For heavily loaded roofs (snow or ponding), account for increased tributary area and possible delayed drainage.
Sample Leader Sizing Table (Quick Reference)
| Leader Diameter (in) | Approx. Capacity (gpm) |
|---|---|
| 3 | 30–75 (depends on inlet and drop) |
| 4 | 75–200 |
| 6 | 200–500 |
| 8 | 500–1,200 |
These are indicative ranges. Use manufacturer tables and local code charts for exact capacities based on vertical drop and inlet conditions.
Common Mistakes And How To Avoid Them
- Using Incorrect Rainfall Intensity: Always verify the in/hr value required by the local code rather than relying on generic maps.
- Ignoring Tributary Boundaries: Incorrectly assigning area to drains typically under- or oversizes drains and leads.
- Neglecting Inlet Losses: Strainers and grates reduce capacity; factor them into selection.
- Failing To Provide Overflows: Overflows are critical for blocked-drain events and code compliance.
Practical Tips For Design And Installation
Coordinate with roof manufacturers and drain suppliers early. Match drain flange and membrane details to avoid leaks. Use tested drain assemblies and document capacities. Inspect and maintain strainers and overflows regularly to preserve design performance.
References And Resources
Designers should consult the latest International Plumbing Code, manufacturer literature for roof drains, local amendments, and NOAA precipitation data for authoritative rainfall intensities and code compliance.